Hoppa till innehåll
Svenska
  • Det finns inga förslag eftersom sökfältet är tomt.

alarm forwarding by email and readiness

Controller can forward alarms via email.

If devices and connections are working, here are the definition for settings:

  1. To "Internet connection" choose 4g/3g (WWAN) settings
  2. To "Name server (DNS)" give as address a working name server, e.g 8.8.8.8 by Google
  3. Delete other "default gateway" definitions (they cannot be used at the same time)
  4. Make sure that the device gets a "Public IP address" address that has the present date
  5. Solve the internet operator from the "IP address" part of the i4g/3g (WWAN) settings (here it is DNA). The instructions to solve the operator.


---
6. Give working SMTP settings and remember to give a real and individualized name as the sender name.

---
7. Create an alarmdevice with the recipient's email.

--- 
8. Create an alarmgroup and activate the alarmdevice to this group.

---
9. Connect an alarm point to the alarmgroup.


---
10. Test the alarm and check its functionality from EMail alarm log.

---